Characteristics
Construction
Type : multicore cable
Core : type 200 pure nickel core as per ASTM B160
Insulation : THS 1400 type composite: mica and coated mineral fibre, PTFE or polyimide tapes (optional)
Electrical screen : optional: nickel-plated copper braid
Armour : optional: AISI 304 stainless steel outer shielding
Sheath : THS 1400 type composite mica and coated mineral fibreglass
Production
Standard : 2x au 7x (depends on cross sections), 0.5 to 6 mm²
Options : please consult our data sheet FT 3304
Application
General use : recommended for zones subject to high temperature peaks (sporadic flames, etc.) and moderately high continuous operating temperatures
General characteristics
Further thermal information : products can withstand conditions and temperatures that no other standard cable on the market would ever be able to withstand
Thermal characteristics
Continuous operating temperature : +700°C to +1200°C (indicative values)
Electrical characteristics
OperatingVoltage : 300 / 500V to 600 / 1000V
Test voltage : 1500 V to 2500 V
Approvals - Standards
Flame retardant, test on bunched cables : IEC 60332-3 (please consult us)
Flame retardant : IEC 60332-1-2 / EN 60332-1-2 /NF C 32-070 test C2
Fire resitance, circuit integrity : IEC 60331-11/21 (please consult us)
Others : nickel type 200, as per standards DIN 17753, DIN 17740 and ASTM B160