Characteristics
Construction
Type : multi-pair cable
Core : rigid bare copper Ø 9/10 mm
Insulation : EI2 fire resistant elastomer
Electrical screen : aluminium/PET tape, continuity wire
Sheath : halogen free flame-retardant polyolefine
Colour of outer cable sheath : orange
Production
Standard : 1 paire to 5 pairs
Options : please consult our data sheet FT 4105
Application
Construction and infrastructure : vital circuits as per the Royal decree of 25 April 2013
General characteristics
Bending radius : minimal 10 x D
Thermal characteristics
Continuous operating temperature : +90°C (maximum core temperature)
Electrical characteristics
OperatingVoltage : 100 / 170V
Approvals - Standards
Fire resistance : FR1 as per NBN EN 50200 / NBN EN 50362 and FR2 as per NBN 713-020/A3
Fire retardant : F2 as per NBN EN 50266-2-4
Flame retardant : F1 as per NBN EN 60332-1-2
Low toxicity : SA as per NBN EN 60754-2
Low smoke : SD as per NBN EN 61034
Others : range approved by the Belgian Fire Safety Institute (ISIB)