Characteristics
Construction
Type : multicore cable
Core : flexible bare copper - class 5 as per IEC 60228
Insulation : PVC as per NF C 32-090
Electrical screen : optional: please consult our data sheet for further information
Shielding : optional: please consult our data sheet
Armour : optional: please consult our data sheet
Sheath : hydrocarbon resistant PVC - type ST1 as per IEC 60502-1
Colour of outer cable sheath : green
Production
Standard : 2x au 37x, 0.34 to 2.5 mm²
Options : please consult our data sheet FT 6503
Application
High-risk sites : cables for power stations, high risk sites or nuclear plants
General characteristics
Chemical behaviour : excellent resistance to aliphatic hydrocarbons as per NF M 87-202, excellent resistance to mineral oil in IRM 902, good resistance to acid and base
Resistance to water : type AD7 as per IEC 60529 without immersion of ends
Thermal characteristics
Continuous operating temperature : -30°C to +80°C
Electrical characteristics
OperatingVoltage : 450 / 750V
Test voltage : 2500 V
Approvals - Standards
Flame retardant : IEC 60332-1-2 / EN 60332-1-2 /NF C 32-070 test C2
High-risk : inspired of standard NF M- 87-202 for oil industry
Others : NF C 32-090