Characteristics
Construction
Type : single core cable
Core : flexible bare copper - class 5 as per IEC 60228
Insulation : silicone rubber, type S 95
Electrical screen : optional: please consult our data sheet for further information
Shielding : optional: please consult our data sheet
Armour : optional: please consult our data sheet
Sheath : HFFR - type SHF1
Colour of outer cable sheath : orange
Production
Standard : 1.5 to 300 mm²
Options : please consult our data sheet FT 6605
Application
High-risk sites : cables for power stations, high risk sites or nuclear plants
General characteristics
Weather conditions : resistance to UV ≥ 2000 hours as per EN 1647
Chemical behaviour : good resistance to acid and base, excellent resistance to aliphatic hydrocarbons
Resistance to water : type AD7 as per IEC 60529 without immersion of ends
Further thermal information : maximum core temperature +95°C
Thermal characteristics
Continuous operating temperature : -30°C to +80°C
Electrical characteristics
OperatingVoltage : 600 / 1000V
Test voltage : 3500 V
Approvals - Standards
Marine, naval : IEC 60092-353, IEC 60092-360
Fire resistance : IEC 60331-21
Fire retardant : NF C 32-070 test C1
Flame retardant, test on bunched cables : IEC 60332-3-22 / EN 60332-3-22
Flame retardant : IEC 60332-1-2 / EN 60332-1-2 /NF C 32-070 test C2
Halogen free : IEC 60754-1 / EN 60754-1
Low toxicity : IEC 60754-2 / EN 60754-2
Low smoke : IEC 61034-2 / EN 61034-2